RADIOACTIVE AIR FILTRATION PLANTS WITH AEROSOL AND IODINE CLEANING AF.27.00.00.00.000

GENERAL DESIGNER
State Scientific Center of the Russian Federation – Institute of Physics Power Engineering named after A.I.Leypunsky.
SPECIFICATIONS
Nominal capacity by air, m3/h
UFK-3500
UFK-7000
UFK-105003500
7000
10500Cleaning efficiency at nominal air flow rate, %
- radioactive aerosols
- molecular iodine
- organic iodine compounds (methyl-iodide-131)
99,97
99,9
99Working temperature of air, 0C from –10 to +150 Inlet relative humidity of air, % 100 (droplets) Aerodynamic resistance to medium flow, Pa
- initial
- maximum permissible
2400
5000Total power of electric heaters, kW
UFK-3500
UFK-7000
UFK-10500
15
30
45Assigned service life of housing structures 50 years Assigned service life till overhaul, h 40 000 Average time between failures, min., h 8 900 Average time of operability recovery, max., h 24 Overall dimensions of UFK-3500 plant, mm (height*width*length) 1396 * 960 * 5240 Weight, kg
UFK-3500
UFK-7000 (two-floor configuration)
1765
3830Technical requirements E 045.6964
HIGH-EFFICIENCY FILTERING UNITS
HAVEN’T FOUND A REQUIRED FILTER?
If you failed to find a filter that would fit your parameters, we can manufacture it specially for you!